Item |
Rated current (mA) |
Coil resistance (Ω) |
Coil inductance (H) |
Must- operate voltage |
Must- release voltage |
Max. voltage |
Power consumption (VA, W) |
|||
---|---|---|---|---|---|---|---|---|---|---|
Rated voltage | 50 Hz | 60 Hz |
Armature OFF |
Armature ON |
Percentage of rated voltage | |||||
AC | 24 | 53.8 | 46 | 180 | 0.69 | 1.3 | 80% max.*1 | 30% min.*2 | 110% |
Approx. 1.1 (at 60 Hz) |
100/110 | 11.7/12.9 | 10.0/11.0 | 3750 | 14.54 | 24.6 |
Approx. 0.9 to 1.1 (at 60 Hz) |
||||
200/220 | 6.2/6.8 | 5.3/5.8 | 12950 | 54.75 | 94.07 | |||||
220/240 | 5.2/6.2 | 4.3/5.0 | 15920 | 83.5 | 136.4 | |||||
DC | 24 | 36.3 (37.7) | 662 (636) | 3.2 | 5.72 | 10% min.*2 | Approx. 0.9 |
Note:
1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20% for the
AC rated current and +15% for the DC coil resistance.
2. The AC coil resistance and inductance values are reference values only (at 60 Hz).
3. Operating characteristics were measured at a coil temperature of 23°C.
4. The values in parentheses for the rated currents and coil voltages of DC coils are for models with LED operation
indicators.
5. The maximum voltage capacity was measured at an ambient temperature of 23°C.
*1. There is variation between products, but actual values are 80% max.
The Relay will operate if 80% or higher of the rated voltage is applied. However, to achieve the specified characteristics,
apply the rated voltage to the coil.
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure
release, use a value that is lower than the specified value.