HIKARI POWER

OMRON MY4N-GS 220/240VAC ราคา 135 บาท

฿120.00
OMRON MY4N-GS 220/240VAC ราคา 135 บาท
เหลือ 0 ชิ้น
ซื้อเลย
หยิบลงตะกร้า
  • หมวดหมู่ : Omron
  • รหัสสินค้า : 002538

รายละเอียดสินค้า OMRON MY4N-GS 220/240VAC ราคา 135 บาท

OMRON MY4N-GS 220/240VAC ราคา 135 บาท

Mechanical Indicators Added as a Standard Feature to Our Bestselling MY General-purpose Relays

Operating Coil

Item Rated current 
(mA)
Coil 
resistance
(Ω)
Coil inductance 
(H)
Must- 
operate
voltage
Must- 
release
voltage
Max. 
voltage
Power 
consumption
(VA, W)
Rated voltage 50 Hz 60 Hz   Armature
OFF
Armature
ON
Percentage of rated voltage
AC 24 53.8 46 180 0.69 1.3 80% max.*1 30% min.*2 110% Approx. 1.1 
(at 60 Hz)
100/110 11.7/12.9 10.0/11.0 3750 14.54 24.6 Approx. 0.9 to 
1.1 (at 60 Hz)
200/220 6.2/6.8 5.3/5.8 12950 54.75 94.07
220/240 5.2/6.2 4.3/5.0 15920 83.5 136.4
DC 24 36.3 (37.7) 662 (636) 3.2 5.72 10% min.*2 Approx. 0.9

Note: 
1. The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/−20% for the 
    AC rated current and +15% for the DC coil resistance. 
2. The AC coil resistance and inductance values are reference values only (at 60 Hz). 
3. Operating characteristics were measured at a coil temperature of 23°C. 
4. The values in parentheses for the rated currents and coil voltages of DC coils are for models with LED operation 
     indicators. 
5. The maximum voltage capacity was measured at an ambient temperature of 23°C. 

*1. There is variation between products, but actual values are 80% max. 
      The Relay will operate if 80% or higher of the rated voltage is applied. However, to achieve the specified characteristics, 
      apply the rated voltage to the coil. 
*2. There is variation between products, but actual values are 30% minimum for AC and 10% minimum for DC. To ensure 
       release, use a value that is lower than the specified value.

Contacts

  2 poles 4 poles
  Resistive load Inductive load 
(cos φ = 0.4, L/R = 7 ms)
Resistive load Inductive load 
(cos φ = 0.4, L/R = 7 ms)
Contact configuration DPDT 4PDT
Contact structure Single
Contact material Ag
Rated load 5 A at 220 VAC 
5 A at 24 VDC
2 A at 220 VAC 
2 A at 24 VDC
3 A at 220 VAC 
3 A at 24 VDC
0.8 A at 220 VAC 
1.5 A at 24 VDC
Rated carry current 5 A   3 A  
Maximum contact voltage 250 VAC, 125 VDC 250 VAC, 125 VDC
Maximum contact current 5 A 3 A
Maximum switching 
capacity
1,100 VA 
120 W
440 VA 
48 W
660 VA 
72 W
176 VA 
36 W
Minimum load 
(reference values)*
1 mA at 5 VDC
* These values are guides for the switchable limits for minute load levels, such as in electronic circuits. Actual characteristics may be different. 
These values will depend on the switching frequency, atmosphere, and expected reliability level. Confirm applicability in the actual system under actual application conditions.