Feed-through terminal block, Connection method: Screw connection, Cross section: 2.5 mm² - 25 mm², AWG: 14 - 4, Width: 12.2 mm, Color: gray, Mounting type: NS 35/7,5, NS 35/15, NS 32
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Potentials | 1 |
| Nominal cross section | 16 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum load current | 101 A (with 25 mm² conductor cross section) |
| Nominal current IN | 76 A |
| Nominal voltage UN | 800 V |
| Open side panel | Yes |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 2.5 mm² / 0.7 kg |
| 16 mm² / 2.9 kg | |
| 25 mm² / 4.5 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 2.5 mm² |
| Tractive force setpoint | 50 N |
| Conductor cross section tensile test | 16 mm² |
| Tractive force setpoint | 100 N |
| Conductor cross section tensile test | 25 mm² |
| Tractive force setpoint | 135 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 32 |
| Setpoint | 10 N |
| Result of voltage-drop test | Test passed |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 16 mm² |
| Short-time current | 1.92 kA |
| Conductor cross section short circuit testing | 25 mm² |
| Short-time current | 3 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1 = 5 Hz to f2 = 150 Hz |
| ASD level | 0.02 g²/Hz |
| Acceleration | 0,8 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 5 g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
120 °C |


This website uses cookies (Learn more) and has a privacy policy (Learn more).