| Model | K2CM-Q2L | |
|---|---|---|
| Current range | 8-26 A | |
| Motor circuit | Rated insulation voltage | AC500V |
| Rated operating voltage | AC200/220 V, 400 / 440 V | |
| Control power circuit | Rated insulation voltage | AC500V |
| Rated operating voltage | AC100/110/120-V, 200 / 220 / 240-V, 400 / 440 V | |
| Output relay circuit | Rated insulation voltage | AC500V |
|
Rated operating voltage and Current |
Contact 1: AC120V/2 A, AC240V/1 A, AC440V/0.5A, DC110V/0.2A, DC220V/0.1A Contact 1: AC120V/5 A, AC240V/2 A, AC440V/1 A, DC110V/0.2A, DC220V/0.1A |
|
| Villa contact capacity | 11 class, AC DC 11 grade * 1 | |
| Contact configuration | a1b 1 * 2 1 c (voltage-phase detection type) | |
| Input circuit | Rated operational current | AC 2-160 A penetrate the ( 1 ) |
| Rated frequency | 50 / 60 Hz | |
| Acceptable range |
Control power supply Working voltage |
85 to 110% of the rated voltage However, phase successfully work at 50% of rated voltage when the. |
| Frequency | 95-105% of the rated frequency | |
| Power consumption | Action front (50 Hz) 3 VA, works at 50 Hz 5 VA | |
| Mass | 780-800 g | |
| Case color | Munsell 5y7/1 | |


This website uses cookies (Learn more) and has a privacy policy (Learn more).