HIKARI POWER

SCHNEIDER LV429637

฿0.00
SCHNEIDER LV429637
เหลือ 0 ชิ้น
  • หมวดหมู่ : Stock_3E
  • รหัสสินค้า : 003757

รายละเอียดสินค้า SCHNEIDER LV429637

range
Compact
 
product name
Compact NSX
 
product or component type
Circuit breaker
 
device short name
Compact NSX100F
 
device application
Distribution
 
poles description
3P
 
protected poles description
3t
 
network type
AC
 
network frequency
50/60 Hz
 
[In] rated current
100 A ( 40 °C )
 
[Ui] rated insulation voltage
800 V AC 50/60 Hz
 
[Uimp] rated impulse withstand voltage
8 kV
 
[Ue] rated operational voltage
690 V AC 50/60 Hz
 
breaking capacity code
F
 
breaking capacity
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 600 V AC 50/60 Hz conforming to UL 508
25 kA at 480 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
 
[Ics] rated service breaking capacity
Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 35 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 36 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Ics 4 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 85 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Ics 12.5 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
 
suitability for isolation
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2
 
utilisation category
Category A
 
trip unit name
TM-D
 
trip unit technology
Thermal-magnetic
 
trip unit protection functions
LI
 
trip unit rating
16 A ( 40 °C )
 
protection type
Overload protection (thermal)
Short-circuit protection (magnetic)
 
pollution degree
3 conforming to IEC 60664-1