| Model | NF32-SVF | |||
| Frame (A) | 30 | |||
|
Rated current In(A) Rated ambient temperature 40 deg. CEL (45 deg. CEL for marine use) |
3A (NF32-SVF 3P 3A) 5A (NF32-SVF 3P 5A) 10A (NF32-SVF 3P 10A) 15A (NF32-SVF 3P 15A) 20A (NF32-SVF 3P 20A) 30A (NF32-SVF 3P 30A) |
|||
| Number of poles | 3 | |||
| Rated insulation voltage Ui (V) | 440 | |||
| Rated short-circuit breaking capacities (kA) |
JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (Icu/Ics) |
AC | 690V | - |
| 500V | - | |||
| 440V | 2.5/2.5 | |||
| 415V | 5/5 | |||
| 400V | 5/5 | |||
| 380V | 5/5 | |||
| 230V | 7.5/7.5 | |||
| 200V | 7.5/7.5 | |||
| DC | 250V | - | ||
| 125V | 10/10 | |||
| Rated impulse withstand voltage Uimp(kV) | 6 | |||
| Current | AC/DC compatible | |||
| Suitabillity for isolation | Compatible | |||
| Reverse connection | - | |||
| Number of operating cycles | Without current | 10,000 | ||
| With current(440VAC) | 6,000 | |||
| Utilization category | A | |||
| Pollution Degree | 3 | |||
| EMC environment condition (environmet A or B) | N/A | |||
| Mass of front-face type(kg) | 0.4 | |||
| CE marking | TUV approval | |||
| CCC recognition | Recognition in process | |||
| Marine use approval (NK, LR, ABS, GL) | - | |||
| Automatic tripping device | Thermal-magnetic | |||
| Trip button | Equipped | |||


This website uses cookies (Learn more) and has a privacy policy (Learn more).